Spain adopts energy and water rules for data centers

The main requirements generally apply to projects with at least 10 MW of grid-access capacity, and covered pending applicants have three months to show compliance.

D
Nov 23, 2026 · 2 min read

Spain’s Council of Ministers approved new electricity and water rules for data centers on November 20. Royal Decree 1032/2026 took effect November 22, a day after its November 21 publication in Spain’s official gazette.

The main rules generally apply at 10 megawatts of grid-access capacity or more. Data centers at the same site under the same ownership count together. The rules cover new, pending or suspended grid-access applications and permitted projects that have yet to connect.

Covered operators generally must cover 80% of their total electricity use through qualifying renewable self-consumption or forward contracts of at least six years with producers using facilities in Spain. Qualifying plants generally need a commissioning certificate dated no more than 36 months before the data center signs its grid-access contract or first uses the relevant electricity. Photovoltaic plants of any age can qualify if they had no signed forward renewable power contract on November 22.

A separate rule generally requires at least 80% of each hour’s electricity use to be matched with renewable generation in the same hour. Sites that start operating before December 31, 2030, can opt into a five-year transition from the effective date if approved for the Automatic Power Reduction System and can cut grid draw to zero on the grid operator’s signal. The transition requires 60% matching in peak tariff hours through 2028, then 70% in peak hours and 60% in shoulder hours from 2029 until it ends.

For each kilowatt-hour used by IT equipment, the general interim limits are 1.25 kilowatt-hours of total site energy and 0.1 liters of water input. Sites have two years from startup to reach the energy target and one year for water. The decree requires the EU’s Class A water-efficiency label once it applies and Spain’s highest energy-efficiency rating once its climate-adjusted method is in use.

Covered pending applicants have three months from November 22 to show compliance. Projects that had permits but lacked a physical grid link or a signed grid-access contract on that date generally have six months to show compliance with the sustainability rules or lose their permits. Those that will host high-category public information systems have 12 months to meet separate digital-sovereignty requirements. Qualifying European strategic projects have separate terms.

The decree excludes facilities dedicated solely to defense, civil protection or public security, as well as facilities owned by or attached to state public-sector entities designated as critical operators.

Annual sustainability reports are due before May 15 for sites with at least 500 kilowatts of installed IT equipment power, regardless of grid-access capacity.